How far should an AC condenser be from the house?
The back of the unit can almost touch the wall. The side with the valves and the air above it cannot.
On this page (8 sections)
- What a condenser is, and why each side gets its own number
- Six manuals: 4 to 10 in at the back, 10 to 30 in at the service side
- Where "2 feet from the house" comes from
- The building code: no wall gap, a 30 x 30 in working space
- Worked through: one side yard 48 in wide
- Above the unit: 48 to 60 in, and why a deck is the usual problem
- Two units side by side: 10 to 24 in
- Where these figures stop applying
Short answer
6 to 12 in (15 to 30 cm) from the house for a central AC condenser, and 4 in (100 mm) for a mini split outdoor unit, by the makers' manuals. That is the gap at the back only. The side with the valves and the control box needs 18 to 30 in (46 to 76 cm), and anything above a condenser should be 48 to 60 in (1.22 to 1.52 m) over its top. Two units side by side need 10 to 24 in between them. The IRC sets no gap to the wall at all.
The numbers, at a glance
- Central AC condenser, back to the wall
- 6 to 12 in (15 to 30 cm)Carrier 6 in on one side, Lennox 6 in, Goodman 10 in
- Mini split outdoor unit, back to the wall
- 4 in (100 mm)Mitsubishi, Fujitsu and Daikin; air enters at the back
- Service side, central condenser
- 18 to 30 in (46 to 76 cm)Goodman 18 in, Carrier 24 in, Lennox 30 in
- Service side, mini split
- 14 in (350 mm)Mitsubishi MUZ-GS24 valve side; Fujitsu 10 in, Daikin 250 mm
- Clear above a central condenser
- 48 to 60 in (1.22 to 1.52 m)Carrier and Lennox 48 in; Goodman 60 in to an obstruction
- In front of a mini split's fan
- 20 to 24 in (500 to 600 mm)Mitsubishi 20 in if two other sides are open; Fujitsu 24 in
- Between two units
- 10 to 24 in (25 to 61 cm)Fujitsu 10 in, Goodman 20 in, Carrier and Lennox 24 in
- IRC working space at the control side
- 30 x 30 in (762 x 762 mm)Level; IRC M1305.1
- IRC gap to the house wall
- NoneThe code points to the manual (M1401.1)
A central AC condenser can sit 6 to 12 in (15 to 30 cm) from the house, and a mini split outdoor unit 4 in (100 mm). Those are the makers' figures, from six installation manuals. But they are the gap at the back only. The side with the valves and the control box needs 18 to 30 in (46 to 76 cm). Anything above a central condenser should be 48 to 60 in (1.22 to 1.52 m) over its top. The building code sets no gap from the wall at all. It asks for a working space at the control side and sends you to the manual for the rest. The rest of the yard is in outdoor room dimensions.
What a condenser is, and why each side gets its own number#
Most home air conditioning is a split system. One part sits indoors and cools the air, and the other sits outside and throws the heat away. That outdoor part is the condenser, or condensing unit: a box holding the compressor, a large coil and a fan. A mini split is a split system without ducts, and its outdoor unit is a flatter box with the fan in its front face.
The two kinds move air in different ways, and that sets the clearances.
- A central condenser draws air in through the coil on its sides and blows it straight up out of the fan on top. Lennox's slab drawing marks the top as "discharge air".
- A mini split outdoor unit draws air in at the back and one side and blows it out of the front. Mitsubishi's base drawing labels the back and left side "air inlet" and the front "air outlet".
A clearance is the free space a maker asks for between its cabinet and anything solid: a wall, a fence, a shrub or another unit. Every figure here is measured from the outside of the cabinet. The service side is where the technician works. On a central condenser it is the corner with the control box and the refrigerant valves. On a mini split it is the side where the pipes connect.
So there is no single "distance from the house". Each face of the unit has its own number, and the manuals give the smallest one to the back.
Six manuals: 4 to 10 in at the back, 10 to 30 in at the service side#
These are the figures as each manual prints them. Several only draw them, so they are read here from the drawings.
| Unit | Closest side (back to the house) | Other sides | Service side | Above | Between units |
|---|---|---|---|---|---|
| Carrier 24ACB, 24ACC (central) | 6 in (152 mm), one side only | 12 in (305 mm) | 24 in (610 mm) | 48 in (1,219 mm) | 24 in (610 mm) |
| Lennox ML14XC1 (central) | 6 in (152 mm), one side only | 12 in (305 mm) and 36 in (914 mm) | 30 in (762 mm) | 48 in (1,219 mm) | 24 in (610 mm) |
| Goodman R-32, residential (central) | 10 in (254 mm) | 10 in (254 mm) | 18 in (457 mm) | 60 in (1,524 mm) to an obstruction | 20 in (508 mm) |
| Mitsubishi MUZ-GS24 (mini split) | 4 in (100 mm) | 4 in (100 mm) at the left | 14 in (350 mm) | Open; 20 in (500 mm) if front and sides are open | Not given as one figure |
| Daikin RXF24 (mini split) | More than 100 mm (3 15/16 in) | More than 50 mm (1 15/16 in) | 250 mm (9 13/16 in) from a wall | 300 mm (11 13/16 in) of work space below a ceiling | Not stated |
| Fujitsu R32 outdoor unit (mini split) | 4 in (100 mm) | 4 in (100 mm) | 10 in (250 mm) | 24 in (600 mm) to a roof | 10 in (250 mm) |
Three things stand out.
Only one side gets the small figure. Carrier's words are "a 6-in. (152.4 mm) clearance on 1 side of unit and 12-in. (304.8 mm) on all remaining sides". Lennox is stricter, allowing 6 in on "the final side", 12 in on one other, 36 in on another, and 30 in "on one of the sides adjacent to the control box". So a Lennox unit can have walls close on two sides, at 6 in and 12 in, but never on three.
The mini split's front is the side that matters. Mitsubishi marks the front and top "clear", with two notes: the front can drop to 20 in (500 mm) "when any 2 sides of left, right and rear of unit are clear", and the top to 20 in "when front and sides of unit are clear". Fujitsu draws 24 in (600 mm) in front wherever a wall faces the fan. Daikin asks more than 350 mm (13 3/4 in) to a wall at the outlet, and that wall may be no taller than 1,200 mm (47 1/4 in).
Goodman says what the numbers are for. Its figures "meet requirements for air circulation only. Consult all appropriate regulatory codes prior to determining final clearances." It also says "corner installations are strongly discouraged". Fujitsu warns that less space than it shows "could cause a short circuit", meaning the unit pulls its own hot exhaust back in, and Mitsubishi says the efficiency of power usage "may fall about 10%" where poor ventilation causes it.
Where "2 feet from the house" comes from#
The figure most often repeated is 24 in, and it is in the manuals, but it is not the gap to the house. In Carrier's manual, 24 in (610 mm) is the service end and the gap between two units. In Lennox's, 24 in is also the gap between two units. Lennox's service side is 30 in (762 mm), not 24 in, which is a figure some summaries of that manual get wrong.
So both answers are in print. The smaller one, 6 to 12 in, is the back of the unit against the wall, and the larger one, 18 to 30 in, is the side a technician kneels at.
The building code: no wall gap, a 30 x 30 in working space#
The International Residential Code (IRC) does not say how far a condenser must be from the house. First, it hands the job to the maker. M1401.1 says heating and cooling equipment "shall be installed in accordance with the manufacturer's instructions and the requirements of this code". So the clearances in the manual become what the inspector checks.
Second, it asks for room to work. M1305.1 says appliances must be reachable "without removing permanent construction, other appliances, or any other piping or ducts". It adds: "A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to service an appliance." That is the IRC's one figure for an outdoor unit, and it sits on the control side, not the back.
Third, it has a rule for the base. M1305.1.3.1 says equipment "supported from the ground shall be level and firmly supported on a concrete slab or other approved material extending not less than 3 inches (76 mm) above the adjoining ground." In the 2021 text that rule sits under the heading "Appliances Under Floors". The manuals ask for a firm, level base in the open yard anyway. Goodman wants "a solid, level foundation that will not shift or settle". Lennox allows its slab to slope at most 2 in per 5 ft (50 mm per 1.5 m), away from the house. Fujitsu, in snowy areas, wants a stand "at or above the anticipated snow depth".
Goodman adds one more point about the pad. To cut sound carried into the house, "the foundation slab should not be in contact with or be an integral part of the building foundation."
Worked through: one side yard 48 in wide#
Take a side yard 48 in (122 cm) wide, from the house wall to a fence. Walk a central condenser and then a mini split through it.
The condenser. Suppose it is a Lennox ML14XC1-036. Its manual gives the cabinet as 28 1/4 in (718 mm) across and 33 1/4 in (845 mm) tall. Suppose it is square in plan.
- The back. Set it 6 in (152 mm) from the house, the "final side" Lennox allows at 6 in.
- The fence side. The front face then sits 6 + 28 1/4 = 34 1/4 in from the wall. That leaves 48 - 34 1/4 = 13 3/4 in (349 mm) to the fence. Lennox needs 12 in on one side, so this passes by 1 3/4 in.
- The two ends. They run along the yard, so they can take the 30 in (762 mm) and the 36 in (914 mm), and the IRC's 30 x 30 in fits in the first. The control box has to face one of the ends. If it faces the fence, the 30 in cannot fit and the plan fails.
So along the wall the unit claims 30 + 28 1/4 + 36 = 94 1/4 in (2.39 m).
The mini split. Now swap in a Mitsubishi MUZ-GS24. Its base drawing gives the body as 33 1/16 in (840 mm) wide and 13 in (330 mm) deep.
- The back. 4 in (100 mm) from the house wall.
- The front. It sits 4 + 13 = 17 in from the wall, which leaves 31 in (79 cm) to the fence. Mitsubishi asks 20 in (500 mm) when two of the left, right and rear are clear, and here the left and right are open, so this passes.
- The ends. 4 in (100 mm) at the left and 14 in (350 mm) at the valve side, on the right.
Along the wall that is 4 + 33 1/16 + 14 = about 51 in (1.30 m).
Above the unit: 48 to 60 in, and why a deck is the usual problem#
A central condenser blows its hot air straight up, so the space above it matters as much as the space beside it. Carrier and Lennox both ask 48 in (1,219 mm) "above unit". Goodman asks for the top to be "completely unobstructed" where possible. Where something must be overhead, it wants "a minimum of 60 inches between the top of the unit and the obstruction(s)".
That is a real height. Take the Lennox ML14XC1-036 at 33 1/4 in (845 mm) tall: with 48 in on top, the lowest thing above must be 81 1/4 in (2.06 m) over the pad. A deck with its joists 7 ft (2.13 m) up passes, and one at 6 ft (1.83 m) does not. The joist and beam depths that set that height are in deck sizes and railing heights.
Mini splits blow sideways, so their top figures are smaller. Fujitsu draws a roof 24 in (600 mm) or more above the unit, with the front left open, and Daikin asks 300 mm (11 13/16 in) of work space below a ceiling.
Eaves bring a second rule. Carrier says to place the unit "so water, snow, or ice from roof or eaves cannot fall directly on unit". A unit tucked under a gutterless roof edge can meet every clearance and still fail that one.
Two units side by side: 10 to 24 in#
A house with two systems needs a gap between the outdoor units as well.
| Units | Gap between cabinets | Source |
|---|---|---|
| Two Carrier 24ACB or 24ACC | 24 in (610 mm) | Carrier manual |
| Two Lennox ML14XC1 | 24 in (610 mm) | Lennox manual |
| Two Goodman residential units | 20 in (508 mm) | Goodman table, "AA" |
| Two or three Fujitsu outdoor units | 10 in (250 mm); three in a row at most | Fujitsu manual |
Where two different makes sit side by side, use the larger of the two figures. That is the site's rule, since neither manual covers the other unit. Mitsubishi adds one case: never set a unit where it takes in the "outlet air discharged by other units directly". So two mini splits should not face each other across a narrow gap.
Where these figures stop applying#
The figures here are for the six models named, from the manuals linked. Other models print other figures, so read your own. The IRC text is the 2021 edition as Colorado adopted it. Your state or city may adopt another edition or add rules of its own, which this page does not cover. Where your inspector or installer asks for more than a manual does, that governs.
This page is about airflow and service space. It does not cover the electrical disconnect, the refrigerant line run, rooftop units or units on wall brackets.
Other things near the unit keep their own rules. A propane cylinder's relief valve stays 5 ft (1.5 m) from exterior sources of ignition, and the fire code does not say whether a condenser counts as one, so ask your gas supplier; the rules are in how far a propane tank has to be from the house. A standby generator sets its own gaps to the wall and to openings, in how far a generator should be from the house. Lennox asks that exhaust from dryers, water heaters and furnaces be "directed away from the outdoor unit", because condensation from it on the steel cabinet will "diminish unit performance and longevity". Dryer vent terminals are placed in dryer venting dimensions and clearances.
Noise has no figure in any manual read here. Carrier says to keep the unit away from "windows, patios, decks, etc." where its sound may disturb people, Lennox prints "Install unit away from windows", and Daikin says to avoid places "near bedrooms". So plan the unit before the seating in patio sizes and layouts, not after. Metric figures are the manuals' own where they print them, and conversions otherwise, as imperial and metric dimension systems explains; check your own with the unit converter. Terms such as clearance are defined with others in the glossary, and the codes this site uses are listed under standards and codes.
Frequently asked questions#
How close can an AC condenser be to the house?
Six inches (152 mm) at the back in the Carrier 24ACB and 24ACC and Lennox ML14XC1 manuals, and 10 in (254 mm) in Goodman's R-32 manual. Only one side may be that close. Carrier wants 12 in (305 mm) on every other side and 24 in (610 mm) at the service end. Lennox wants 12 in, 30 in and 36 in on the other three.
How far should a mini split outdoor unit be from the wall?
Four inches (100 mm) behind it, in the Mitsubishi MUZ-GS24 and Fujitsu R32 manuals; Daikin's RXF24 prints more than 100 mm. The back is where the unit draws in air, so do not go closer. The front, where the fan blows out, needs 20 in (500 mm) or more in Mitsubishi's manual and 24 in (600 mm) in Fujitsu's if a wall faces it.
How much space do you need above an AC unit?
Forty-eight inches (1,219 mm) above the top in the Carrier and Lennox manuals. Goodman asks 60 in (1,524 mm) from the top to any obstruction, and says the top should be open where possible. A central condenser blows its air straight up. A deck or roof too low sends that hot air back into the coil.
How far apart should two AC units be?
Twenty-four inches (610 mm) between two central condensers in the Carrier and Lennox manuals, and 20 in (508 mm) in Goodman's residential table. Fujitsu asks at least 10 in (250 mm) between its outdoor units, and no more than three in a row. Measure from cabinet to cabinet, not from pad to pad.
Does the building code say how far an AC unit must be from the house?
No. The IRC sets no gap from the wall. It says equipment goes in by the maker's instructions (M1401.1), so the manual's clearances are what an inspector checks. It also asks for a level working space 30 x 30 in (762 x 762 mm) in front of the control side (M1305.1). Local codes can add more.
Can I put a fence or a screen around my AC unit?
Yes, if it stays outside the manual's clearances. A screen 12 in (305 mm) from a Carrier condenser on three sides meets the airflow figure, but the service end still needs 24 in (610 mm). Goodman calls a unit boxed into a corner "strongly discouraged". Fujitsu notes that a wall further away than its drawing shows counts as no obstacle at all.
Should an AC unit be under a window?
Not if you can help it. Carrier's manual says to keep the unit away from windows, patios and decks where its sound may disturb people. Lennox prints "Install unit away from windows" on its placement drawing, and Daikin says to avoid places near bedrooms. None of them gives a distance. It is a noise rule, not a clearance.
Sources and standards referenced#
- Installation instructions, 24ACB3 and 24ACC6 air conditioners, 1-1/2 to 5 tons Carrier6 in on one side, 12 in on the rest, 24 in at the service end, 48 in above, 24 in between units; keep away from windows, patios and decks; no water or ice from eaves
- Installation instructions, ML14XC1 split system AC unit, 508174-01 Lennox30 in service side by the control box, 36 in, 12 in and 6 in on the others, 48 in on top, 24 in between units; unit sizes; slab slope; dryer and furnace exhausts away from the unit
- Condensing unit, air conditioning, installation and service reference, IOG-4048C (December 2024) Goodman (Daikin Comfort Technologies)Residential minimum airflow clearance: 10 in, 10 in, 18 in, 20 in between units; 60 in to an obstruction above; corners discouraged; slab apart from the house foundation
- Installation manual, MSZ-GS24NA and MUZ-GS24NAHZ Mitsubishi ElectricOutdoor unit 4 in (100 mm) at the rear and left side, 14 in (350 mm) at the valve side; 20 in (500 mm) at the front and top where other sides are open; 13 in (330 mm) deep
- Installation manual, RXF18 and RXF24 outdoor units (3P740831-2E, 2024) DaikinMore than 100 mm at the intake wall, 50 mm at the side, 350 mm to a wall at the outlet (no higher than 1,200 mm), 250 mm from a wall at the piping side, 300 mm below a ceiling
- Air conditioner outdoor unit installation manual, part no. 9300793070-02 (AOUH09KTAP1) Fujitsu General4 in (100 mm) at the rear, 4 in and 10 in (250 mm) at the sides, 24 in (600 mm) at the front, 24 in to a roof above; 10 in between units, three in a row at most; stand above snow depth
- International Residential Code 2021, chapters 13 and 14 (Colorado adoption) International Code Council, via UpCodesM1305.1 30 x 30 in working space at the control side; M1305.1.3.1 ground clearance 3 in (under the heading for appliances under floors); M1401.1 install by the manufacturer's instructions
We cite published codes, industry planning guidelines and manufacturer specifications. Where a figure is our own recommendation rather than a published standard, the text says so. See how we measure.